• DocumentCode
    1031477
  • Title

    Performance Test of the Allgemeine Elektricitats Gesellschaft Free-Jet Air-Blast 220-Kv 2,500-Megavolt-Ampere Reclosing Circuit Breaker

  • Author

    Dovjikov, Alexander ; Diemond, Clifford C.

  • Author_Institution
    Chief of analysis and research unit, engineering division of Bonneville Power Administration, Portland, Ore.
  • Volume
    67
  • Issue
    1
  • fYear
    1948
  • Firstpage
    295
  • Lastpage
    306
  • Abstract
    Tests of a representative sample of this circuit breaker were made on the system of the Bonneville Power Administration in order to provide an opportunity for American manufacturers and operating engineers to study the operation of this circuit breaker in interrupting faults and line charging currents. A single pair of interrupting contacts in open air, ease of contacts visual inspection, maintenance and replacement attracted much attention and favorable comment, particularly from operating engineers. The circuit breaker successfully interrupted fault currents in about six cycles (average) as compared with three cycles of fast oil circuit breakers of American manufacture. Interruption of line charging current, although successful, was accompanied by many restrikes. It is hoped that these tests and the analysis of the test data will facilitate development of an American circuit breaker which will retain the favored features of the European prototype but will be faster in interrupting fault currents and practically free from restrikes in interrupting line charging currents.
  • Keywords
    Circuit breakers; Circuit faults; Circuit testing; Fault currents; Inspection; Manufacturing; Petroleum; Power engineering and energy; Prototypes; System testing;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1948.5059673
  • Filename
    5059673