DocumentCode
1031676
Title
Bonneville Power Administration´s 1100-kV Direct Current Test Project: I - Measurements and Instrumentation
Author
Poland, M.G. ; Belsher, Mi W. ; Osipovich, A.A.
Author_Institution
Bonneville Power Administration
Issue
3
fYear
1967
fDate
3/1/1967 12:00:00 AM
Firstpage
268
Lastpage
277
Abstract
Methods of measurement and analysis of components of a five-mile extra-high-voltage direct-current test line and associated facilities are described. This paper presents new methods of recording and analyzing data secured over a long period of time concerning radio influence, corona loss, insulator leakage, and surge currents. Information secured from these recordings and analysis will be important to the transmission engineer in designing the most economical high-quality EHV dc transmission line.
Keywords
Corona; Current measurement; Data analysis; Design engineering; Information analysis; Instruments; Insulation; Power measurement; Surges; Testing;