DocumentCode
1032231
Title
The Calculation of Double Circuit Outage Rate of Transmission Lines
Author
Sargent, Michael A. ; Darveniza, Mat
Author_Institution
Department of Electrical Engineering, University of Queensland
Issue
6
fYear
1967
fDate
6/1/1967 12:00:00 AM
Firstpage
665
Lastpage
678
Abstract
A method has been developed to predict the probability of a double circuit outage on double circuit lines. Traveling wave techniques are used to account for nonlinearities such as corona, attenuation, and phase conductor flashover as its time iterative approach enables alteration of design parameters at each time increment. A geometrical model technique, involving comparison of lightning voltages measured on the models with those obtained from linear traveling wave calculations, enables realistic estimation of the value ascribed to tower surge impedance, an important parameter in the calculations.
Keywords
Conductors; Corona; Distributed parameter circuits; Flashover; Impedance measurement; Iterative methods; Lightning; Optical attenuators; Solid modeling; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1967.291877
Filename
4073333