DocumentCode :
1032231
Title :
The Calculation of Double Circuit Outage Rate of Transmission Lines
Author :
Sargent, Michael A. ; Darveniza, Mat
Author_Institution :
Department of Electrical Engineering, University of Queensland
Issue :
6
fYear :
1967
fDate :
6/1/1967 12:00:00 AM
Firstpage :
665
Lastpage :
678
Abstract :
A method has been developed to predict the probability of a double circuit outage on double circuit lines. Traveling wave techniques are used to account for nonlinearities such as corona, attenuation, and phase conductor flashover as its time iterative approach enables alteration of design parameters at each time increment. A geometrical model technique, involving comparison of lightning voltages measured on the models with those obtained from linear traveling wave calculations, enables realistic estimation of the value ascribed to tower surge impedance, an important parameter in the calculations.
Keywords :
Conductors; Corona; Distributed parameter circuits; Flashover; Impedance measurement; Iterative methods; Lightning; Optical attenuators; Solid modeling; Voltage;