500-kV Line Design: I - Insulation Characteristics of Towers
Author
Saruyama, Yukio ; Yasui, Mitsuru ; Ikeda, Giichi ; Nagasaki, Shoji ; Mori, Norihiro
Author_Institution
Tokyo Electric Power Company
Issue
9
fYear
1967
Firstpage
1083
Lastpage
1090
Abstract
The results of tests using a full-scale transmission line for the insulation design of the first 500-kV transmission line in Japan (the Boso Line of Tokyo Electric Power Company) are described. Having clarified the switching surge and impulse flashover characteristics of V-string insulator and strain insulator assemblies, installed on a simulated tower with a long gap of three meters or more, insulation was designed which withstands a switching surge of 2.5 per unit and is capable of unbalanced insulation between vertically arranged double circuits. The flashover path, predischarge, etc., of the switching surge was also investigated.
Keywords
Assembly; Capacitive sensors; Circuit simulation; Dielectrics and electrical insulation; Flashover; Insulation testing; Poles and towers; Power transmission lines; Surges; Switching circuits;