• DocumentCode
    1032836
  • Title

    500-kV Line Design: I - Insulation Characteristics of Towers

  • Author

    Saruyama, Yukio ; Yasui, Mitsuru ; Ikeda, Giichi ; Nagasaki, Shoji ; Mori, Norihiro

  • Author_Institution
    Tokyo Electric Power Company
  • Issue
    9
  • fYear
    1967
  • Firstpage
    1083
  • Lastpage
    1090
  • Abstract
    The results of tests using a full-scale transmission line for the insulation design of the first 500-kV transmission line in Japan (the Boso Line of Tokyo Electric Power Company) are described. Having clarified the switching surge and impulse flashover characteristics of V-string insulator and strain insulator assemblies, installed on a simulated tower with a long gap of three meters or more, insulation was designed which withstands a switching surge of 2.5 per unit and is capable of unbalanced insulation between vertically arranged double circuits. The flashover path, predischarge, etc., of the switching surge was also investigated.
  • Keywords
    Assembly; Capacitive sensors; Circuit simulation; Dielectrics and electrical insulation; Flashover; Insulation testing; Poles and towers; Power transmission lines; Surges; Switching circuits;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1967.291791
  • Filename
    4073398