• DocumentCode
    1032960
  • Title

    Influence of Phase Connection and Terminal Conditions on Natural Frequencies of Three-Phase Transformer Windings

  • Author

    Gururaj, B.I.

  • Author_Institution
    Indian Institute of Science
  • Issue
    1
  • fYear
    1968
  • Firstpage
    1
  • Lastpage
    12
  • Abstract
    With the increasing use of extra high-voltage transmission in power system expansion, the manufacturers of power apparatus and the electric utilities are studying the nature of overvoltages in power systems due to lightning and, in particular, switching operations. For such analyses, knowledge of the natural frequencies of the windings of transformers under a wide variety of conditions is important. The work reported by the author in a previous paper is extended and equivalent circuits have been developed to represent several sets of terminal conditions. These equivalent circuits can be used to determine the natural frequencies and transient voltages in the windings. Comparison of the measured and the computed results obtained with a model transformer indicates that they are in good agreement. Hence, this method of analysis provides a satisfactory procedure for the estimation of natural frequencies and transient voltages in transformer windings.
  • Keywords
    Equivalent circuits; Frequency estimation; Lightning; Manufacturing; Phase transformers; Power industry; Power system analysis computing; Power system transients; Surges; Transient analysis;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1968.292229
  • Filename
    4073412