DocumentCode
1033825
Title
Ferroresonant Overvoltage Control Based on TNA Tests on Three-Phase Wye-Delta Transformer Banks
Author
Hopkinson, Ralph H.
Author_Institution
General Electric Company, Electric Utility Engineering Operation
Issue
2
fYear
1968
Firstpage
352
Lastpage
361
Abstract
This paper shows possible ferroresonant overvoltages on wye-delta transformer banks during single-phase switching as a function of transformer size and lateral length. Application guide is based on industry standard voltage criteria. Secondary loading and neutral resistor requirements are given. A neutral resistor presents an attractive solution in many cases. Simple to use equations are given to allow application of test data.
Keywords
Capacitance; Control systems; Ferroresonance; Grounding; Power cables; Resistors; Switches; Testing; Transient analysis; Voltage control;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1968.292029
Filename
4073505
Link To Document