DocumentCode :
1034352
Title :
Solid-State, High-Speed Phase-Comparison Relay Based on Zero Crossings: I - Theory
Author :
Robertson, Stuart D.T. ; Meikle, W. Norman
Author_Institution :
Department of Electrical Engineering, University of Toronto
Issue :
3
fYear :
1968
fDate :
3/1/1968 12:00:00 AM
Firstpage :
764
Lastpage :
770
Abstract :
A relay scheme has been developed based on the instantaneous phase current zero crossings. Transient and steady- state unbalances will produce shifts of the phase currents, therefore measurement of the deviation of successive zero crossings from 60 degrees leads to six possible fault indications per cycle. Comparison of the deviation magnitude at either end of a relay zone can be used to locate the fault. This scheme requires no additional delay due to analog filtering. It is shown that all types of faults with zero or finite impedance give at least two and a maximum of six fault indications per cycle.
Keywords :
Circuit faults; Fault currents; Fault detection; Power system modeling; Power system relaying; Power system transients; Relays; Solid state circuits; Transient analysis; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1968.292191
Filename :
4073561
Link To Document :
بازگشت