DocumentCode :
1034719
Title :
Verification Tests of the VEPCO 500-kY System
Author :
Wagner, Charles L. ; Smith, H. Melvin ; Taylor, Edgar R., Jr. ; Laprade, John H.
Author_Institution :
Westinghouse Electric Corporation
Issue :
4
fYear :
1968
fDate :
4/1/1968 12:00:00 AM
Firstpage :
1032
Lastpage :
1044
Abstract :
The results of the first field tests performed to verify the design of the Virginia Electric Power Company 500-kV system are presented. Initial radio influence measurements made on each line section are compared with levels calculated during the design studies. Switching-surge voltages recorded during various normal and abnormal switching conditions are given, and are shown to be well within predicted values. Descriptions are given of the measuring equipment and techniques used for the field tests and for a continual monitoring of the system.
Keywords :
Design engineering; Lightning; Performance evaluation; Power transformer insulation; Printing; Storms; Substations; Surges; System testing; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1968.292080
Filename :
4073600
Link To Document :
بازگشت