DocumentCode :
1034903
Title :
Specific investigations to quantify heavy damage causes on loading resistor modules
Author :
Fofana, I. ; Wasserberg, V. ; Borsi, H. ; Gockenbach, E. ; Farzaneh, M.
Author_Institution :
Univ. du Quebec a Chicoutimi, Que.
Volume :
13
Issue :
3
fYear :
2006
fDate :
6/1/2006 12:00:00 AM
Firstpage :
593
Lastpage :
600
Abstract :
In this paper, premature damage to some static inverter loading resistor modules is analyzed. Furthermore, investigations were carried out to determine the origins and causes of this serious damage occurring on the resistor modules in service. Investigations were preformed on the insulating liquid samples as well as new resistor modules. From the results obtained, it seems that the origin of the damage is from a long-standing, free-burning arc between two resistor windings, following mechanical breakdown
Keywords :
arcs (electric); dielectric liquids; fault diagnosis; invertors; resistors; windings; arc heating; bubbles; dielectric liquid; electric breakdown; fault diagnostic; mechanical breakdown; premature damage; resistor module; static inverter loading; windings; Circuit testing; Dielectric liquids; Dielectrics and electrical insulation; Electric breakdown; Inverters; Manufacturing; Power transformer insulation; Resistors; Voltage; Wiring;