Title :
A Laboratory Investigation of Ferroresonance in Cable-Connected Transformers
Author :
Young, Frank S. ; Schmid, Ronald L. ; Fergestad, Petter I.
Author_Institution :
Westinghouse Electric Corporation
fDate :
5/1/1968 12:00:00 AM
Abstract :
Results of a full scale laboratory investigation into the ferroresonance phenomenon are presented. The investigation consisted of energizing and de-energizing three-phase 13-kV padmounted distribution transformers with single-phase cutouts. Applied cable lengths ranged from 100 to 5000 feet. In addition to three- phase switching, the application of resistive loading from 1 to 4 percent was also investigated as a preventive measure. Results indicate that three-phase switching, the use of a wye-wye transformer with both neutrals grounded, and the presence of secondary load are all effective in the control of ferroresonant overvoltages.
Keywords :
Capacitors; Ferroresonance; Hospitals; Laboratories; Nonlinear circuits; Phase transformers; Power cables; Substation protection; Surges; Testing;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1968.292213