• DocumentCode
    1035697
  • Title

    Isolated-Phase Bus Enclosure Currents

  • Author

    Niemoller, Arthur B.

  • Author_Institution
    SCDE Division, Westinghouse Electric Corporation
  • Issue
    8
  • fYear
    1968
  • Firstpage
    1714
  • Lastpage
    1718
  • Abstract
    In the continuous-enclosure type isolated-phase bus, the enclosure current in amperes is very nearly equal to the conductor current. It lags the conductor current by somewhat less than 180°. The external flux is relatively small, and any induction heating in material or induced volts in instrument or control circuits adjacent to the bus will be negligible. Methods for determining the actual current in the enclosure and the external magnetic field are developed in this paper.
  • Keywords
    Circuits; Conducting materials; Conductors; Equations; Instruments; Magnetic fields; Magnetic materials; Power generation; Skin effect; Temperature control;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1968.292133
  • Filename
    4073701