DocumentCode :
1035697
Title :
Isolated-Phase Bus Enclosure Currents
Author :
Niemoller, Arthur B.
Author_Institution :
SCDE Division, Westinghouse Electric Corporation
Issue :
8
fYear :
1968
Firstpage :
1714
Lastpage :
1718
Abstract :
In the continuous-enclosure type isolated-phase bus, the enclosure current in amperes is very nearly equal to the conductor current. It lags the conductor current by somewhat less than 180°. The external flux is relatively small, and any induction heating in material or induced volts in instrument or control circuits adjacent to the bus will be negligible. Methods for determining the actual current in the enclosure and the external magnetic field are developed in this paper.
Keywords :
Circuits; Conducting materials; Conductors; Equations; Instruments; Magnetic fields; Magnetic materials; Power generation; Skin effect; Temperature control;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1968.292133
Filename :
4073701
Link To Document :
بازگشت