Title :
Thermal Performance of Distribution Transformers in Underground Vaults: II - Mathematical Model
Author :
Whirlow, Donald K. ; Lockie, Arthur M.
Author_Institution :
Westinghouse Electric Corporation
Abstract :
The transient thennal response of buried distribution transformers is analyzed by use of a lumped-parameter model. Curves are presented which show the temperatures in the transformer r during startup and continuous running with typical load cycles, steady loads, and step loads. The effects of earth conductivity y and radiation barriers are considered. Temperatures, time constants, and convection coefficients are found to agree well with experimental measurements.
Keywords :
Earth; Heat transfer; Immune system; Mathematical model; Power system modeling; Temperature; Thermal conductivity; Thermal loading; Thermal resistance; Transformers;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1968.291979