Title :
Report on Survey of Unbalanced Charging Currents on Transmission Lines as Affecting Ground-Fault Neutralizers
fDate :
7/1/1949 12:00:00 AM
Abstract :
The committee finds that the requirement that neutralizers be capable of carrying a continuous circulating current not less than 30 per cent of its rating appears to be sound in view of the foregoing conclusions, and therefore recommends that no change be made.
Keywords :
Costs; Flashover; Inductors; Insulators; Investments; Iron; Lightning; Power cables; Transmission lines; Voltage;