• DocumentCode
    1035811
  • Title

    Fault Surge Versus Switching Surge A Study of Transient Overvoltages Caused by Line-to-Ground Faults

  • Author

    Kimbark, Edward W. ; Legate, Alvin C.

  • Author_Institution
    Bonneville Power Admiinistration
  • Issue
    9
  • fYear
    1968
  • Firstpage
    1762
  • Lastpage
    1769
  • Abstract
    When the improvements in extra-high- oltage power circuit breakers now being studied are realized in practice, over- voltages caused by energization or reenergization of lines can be made so low that the limiting factor determining how much the line insulation may be reduced might become the overvoltage produced by single line-to-ground faults. On lines insulated for levels below twice the normal line-to-ground crest voltage, such faults could develop into double line-to-ground faults, which would be particularly objectionable if single-pole switching were to be employed.
  • Keywords
    Circuit breakers; Circuit faults; Distributed parameter circuits; Insulation; Power system transients; Printing; Shunt (electrical); Surges; Transient analysis; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1968.291981
  • Filename
    4073712