DocumentCode :
1036252
Title :
Loading of Hydrogen-Cooled Generators at Elevated Gas Pressures
Author :
Snell, D.S.
Author_Institution :
General Electric Company, Schenectady, N. Y.
Volume :
69
Issue :
1
fYear :
1950
Firstpage :
186
Lastpage :
204
Abstract :
This paper presents a study, based on calculations and tests, of the heating characteristics of hydrogen-cooled generators at elevated gas pressures, and discusses various criteria for determining the capability of generators at elevated pressures. It is shown that the assumption of constant temperature rise of the windings above cold gas temperature, as a basis for limiting the output at elevated hydrogen pressures (particularly the rise of the armature winding by embedded detector) is misleading, and that a more realistic basis of rating is the assumption of constant total temperature of the winding copper, for constant temperature of ingoing cooling water at different loads and hydrogen pressures.
Keywords :
Character generation; Cooling; Copper; Detectors; Heating; Hydrogen; Machine windings; Machinery; Temperature; Testing;
fLanguage :
English
Journal_Title :
American Institute of Electrical Engineers, Transactions of the
Publisher :
ieee
ISSN :
0096-3860
Type :
jour
DOI :
10.1109/T-AIEE.1950.5060138
Filename :
5060138
Link To Document :
بازگشت