DocumentCode :
1036607
Title :
Determination of Post-Zero Current from Restored Voltage Transient
Author :
Voshall, Roy E.
Author_Institution :
Westinghouse Electric Corporation
Issue :
2
fYear :
1969
Firstpage :
108
Lastpage :
119
Abstract :
The post-zero current that flows in power circuit breakers during the voltage recovery period is calculated from the restored voltage transient, knowing the equivalent circuit for the test circuit. A differential equation for the post-zero current is derived, and numerical methods for solving it by means of an electronic computer are discussed. Data from a typical circuit breaker test are used to illustrate the different numerical methods.
Keywords :
Circuit breakers; Circuit testing; Coaxial components; Current measurement; Electrodes; Integrated circuit measurements; Magnetic field measurement; Plasma measurements; Transformers; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1969.292411
Filename :
4073801
Link To Document :
بازگشت