DocumentCode :
1036759
Title :
Proposed methods to determine fault point X/R ratio for breaker evaluation
Author :
Dartawan, Ketut ; Pierre, Conrad St
Author_Institution :
Power Technol. Inc., Schenectady, NY, USA
Volume :
40
Issue :
4
fYear :
2004
Firstpage :
941
Lastpage :
949
Abstract :
ANSI/IEEE and IEC standards provide procedures that do a fairly good job in obtaining a single fault point X/R ratio that will allow a conservative estimate of the dc component and, therefore, the total fault current flowing in a breaker. However, there are circuit configurations that result in overly conservative or under conservative estimates of the fault X/R ratio. This paper explores alternate methods using the information in a complex impedance network reduction and presents an alternate method that provides comparable X/R ratios and conservatism without the need to preform dual network reductions.
Keywords :
ANSI standards; IEC standards; IEEE standards; circuit breakers; fault currents; ANSI standard; IEC standard; IEEE standard; X/R ratio; breaker evaluation; fault current; fault point; impedance network reduction; ANSI standards; Chemical industry; Circuit faults; Fault currents; Frequency; IEC standards; Impedance; Industry Applications Society; Petroleum; Preforms; $X/R$ ratio; Short-circuit currents;