• DocumentCode
    1036977
  • Title

    Corona Detection Experience in Commercial Production of Power Cables with Extruded Insulation

  • Author

    Eager, George S., Jr. ; Bahder, George ; Silver, David A.

  • Author_Institution
    General Cable Corporation
  • Issue
    4
  • fYear
    1969
  • fDate
    4/1/1969 12:00:00 AM
  • Firstpage
    342
  • Lastpage
    364
  • Abstract
    On the basis of extensive corona detection experience on full reel testing of cables it is proposed that, in addition to corona level, a characteristic designated as "corona factor" be determined on each reel length of high-voltage cable with extruded conductor and insulation shields. The corona factor establishes the relationship between discharges in the cable and voltage stress over a stress range up to several times the operating level. In addition, it is proposed that full reel power factor measurements be made to provide a check on the resistivity of the extruded shields. The use of a novel continuous corona discharge detector in the laboratory to locate defects in the cable core, with insulation semiconducting shield in place, is described.
  • Keywords
    Cable insulation; Conductors; Corona; Insulation testing; Power cables; Power measurement; Production; Reactive power; Stress; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1969.292455
  • Filename
    4073841