• DocumentCode
    1037273
  • Title

    Hydroelectric Generator Excitation Experience at Grand Coulee

  • Author

    Killgore, C.L. ; Holmdahl, N.G.

  • Author_Institution
    Bureau of Reclamation, Denver, Colo.
  • Volume
    69
  • Issue
    2
  • fYear
    1950
  • Firstpage
    855
  • Lastpage
    860
  • Abstract
    1. Experience with the motor-driven exciter at the Grand Coulee Power Plant indicates that automatic transfer of power sources to the motor can be successfully done under full load by removing the motor from a faulty power source and reconnecting it to another power source. 2. However, experience also indicates that the best protection is to provide sufficient power sources so that the loss of one source will not cause the loss of excitation. 3. Additional pilot-exciter voltage-regulation equipment has reduced peak voltages on the generators approximately 1.5 kv on a 13.8-kv base with the possibility of reducing this still further by the addition of more resistance in the high-speed lowering relay circuit in the main exciter field.
  • Keywords
    Hazards; Hydroelectric power generation; Induction motors; Power generation; Power markets; Power supplies; Power system relaying; Switchgear; Synchronous motors; Voltage;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1950.5060235
  • Filename
    5060235