• DocumentCode
    1037308
  • Title

    Desert Measurements of Corona Loss on Conductors for Operation Above 230 Kv

  • Author

    Peterson, W.S. ; Cozzens, Bradley ; Carroll, Joseph S.

  • Author_Institution
    Department of Water and Power, The City of Los Angeles, Calif.
  • Volume
    69
  • Issue
    2
  • fYear
    1950
  • Firstpage
    872
  • Lastpage
    881
  • Abstract
    This paper reports corona loss measurements made under desert conditions on 1.25-inch and 1.4-inch type-HH copper conductor and 1.4-inch conductor. The variations from wattmeter equipment are discussed. Conditions and losses measured indicate that factors, yet unknown, exist in some desert areas that cause corona loss values to occur at considerably lower voltages than would have been anticipated from previous tests in coastal climates. The tests indicate the necessity for use of added liberality in selecting conductor diameter or confirmation by extended field tests of the existence or absence of the phenomena described. The 1.4-inch type-HH conductor showed adequate liberality for desert operation. The 1.4-inch stranded cable, though adequate in coastal or under normal climatic conditions, showed losses which might prove uneconomical under conditions encountered in the desert areas. The 1.25-type-HH cable appeared definitely inadequate for use in desert areas.
  • Keywords
    Area measurement; Conductors; Corona; Laboratories; Loss measurement; Power cables; Sea measurements; Testing; Transmission line theory; Voltage;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1950.5060238
  • Filename