DocumentCode
1037308
Title
Desert Measurements of Corona Loss on Conductors for Operation Above 230 Kv
Author
Peterson, W.S. ; Cozzens, Bradley ; Carroll, Joseph S.
Author_Institution
Department of Water and Power, The City of Los Angeles, Calif.
Volume
69
Issue
2
fYear
1950
Firstpage
872
Lastpage
881
Abstract
This paper reports corona loss measurements made under desert conditions on 1.25-inch and 1.4-inch type-HH copper conductor and 1.4-inch conductor. The variations from wattmeter equipment are discussed. Conditions and losses measured indicate that factors, yet unknown, exist in some desert areas that cause corona loss values to occur at considerably lower voltages than would have been anticipated from previous tests in coastal climates. The tests indicate the necessity for use of added liberality in selecting conductor diameter or confirmation by extended field tests of the existence or absence of the phenomena described. The 1.4-inch type-HH conductor showed adequate liberality for desert operation. The 1.4-inch stranded cable, though adequate in coastal or under normal climatic conditions, showed losses which might prove uneconomical under conditions encountered in the desert areas. The 1.25-type-HH cable appeared definitely inadequate for use in desert areas.
Keywords
Area measurement; Conductors; Corona; Laboratories; Loss measurement; Power cables; Sea measurements; Testing; Transmission line theory; Voltage;
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Transactions of the
Publisher
ieee
ISSN
0096-3860
Type
jour
DOI
10.1109/T-AIEE.1950.5060238
Filename
5060238
Link To Document