Title :
Predetermination of the Radio Noise Level Under Rain of an Extra-High-Voltage Line
Author :
Gary, Claude H. ; Moreau, Marcel R.
Author_Institution :
Direction des Etudes et Recherches d´´Electricitéde France
fDate :
5/1/1969 12:00:00 AM
Abstract :
Radio noise levels under rain of 4-conductor bundles installed at les Renardi??res experimental station have remained remarkably constant during the first two years of operation. These levels are reached as soon as the rain intensity exceeds 0.01 mm /min. It is therefore possible to predetermine accurately the radio noise level under rain of a line equipped with 4-conductor bundles depending on the surface gradient and the radius of the subconductors.
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :