• DocumentCode
    1037825
  • Title

    Open Breaker Protection of EHV Systems

  • Author

    Hileman, Andrew R. ; Wagner, Charles L. ; Kisner, Richard B., Jr.

  • Author_Institution
    Westinghouse Electric Corporation
  • Issue
    7
  • fYear
    1969
  • fDate
    7/1/1969 12:00:00 AM
  • Firstpage
    1005
  • Lastpage
    1014
  • Abstract
    Although the use of line-entrance lightning arresters provides absolute protection for an open breaker condition, it represents a costly installation. No line entrance protection represents some risk of breaker damage. Line entrance rod gaps offer a compromise between these extremes. This paper discusses the probabilities of failures using these three alternatives and describes a procedure whereby the spacing of the line-entrance gap can be determined. Since this procedure depends on the particular configuration of the gap being used, test data are presented on one particular configuration used on a 345-kV system. Based on these data, recommended gap spacings for 345-and 500-kV systems are developed.
  • Keywords
    Arresters; Circuit breakers; Circuit testing; Costs; Flashover; Lightning; Power system protection; Surge protection; Switches; System testing;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1969.292499
  • Filename
    4073937