DocumentCode
1038329
Title
765-kV Station Insulation Coordination
Author
Phelps, James D M ; Pugh, P.S. ; Beehler, James E.
Author_Institution
Americani Electric Power Service Corporation
Issue
9
fYear
1969
Firstpage
1377
Lastpage
1382
Abstract
Specially designed arresters are used in the American Electric Power 765-kV station insulation coordination as a first line of defense against overvoltage. The arresters have the ability to withstand sustained and dynamic overvoltages in excess of their rating. They also have the ability to discharge repetitively. Use of these arresters permitted 1800-kV BIL ratings for transformers, reactors, and circuit breakers. A performance criterion for bus flashover was established in terms of probability. New methods were used to test station insulator withstand and contamination performance.
Keywords
Arresters; Circuit breakers; Circuit testing; Contamination; Dielectrics and electrical insulation; Flashover; Inductors; Insulator testing; Power transformer insulation; Voltage control;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1969.292529
Filename
4073992
Link To Document