DocumentCode :
1038329
Title :
765-kV Station Insulation Coordination
Author :
Phelps, James D M ; Pugh, P.S. ; Beehler, James E.
Author_Institution :
Americani Electric Power Service Corporation
Issue :
9
fYear :
1969
Firstpage :
1377
Lastpage :
1382
Abstract :
Specially designed arresters are used in the American Electric Power 765-kV station insulation coordination as a first line of defense against overvoltage. The arresters have the ability to withstand sustained and dynamic overvoltages in excess of their rating. They also have the ability to discharge repetitively. Use of these arresters permitted 1800-kV BIL ratings for transformers, reactors, and circuit breakers. A performance criterion for bus flashover was established in terms of probability. New methods were used to test station insulator withstand and contamination performance.
Keywords :
Arresters; Circuit breakers; Circuit testing; Contamination; Dielectrics and electrical insulation; Flashover; Inductors; Insulator testing; Power transformer insulation; Voltage control;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1969.292529
Filename :
4073992
Link To Document :
بازگشت