DocumentCode :
1038765
Title :
Comparison of Insulator Types by the Wet Contaminant and Clean Fog Test Methods
Author :
Macchiaroli, Bruno ; Turner, Frederick J.
Author_Institution :
Institute of Electrical Engineering
Issue :
2
fYear :
1970
Firstpage :
190
Lastpage :
197
Abstract :
Withstand and flashover test data are presented for five types of insulators tested by the clean fog method and the wet contaminant method. The insulators were contaminated with a slurry having the proportions of 1 liter of water, 20 grams of Cab-O- Sil, 1 gram of Photo-Flo, and various quantities of salt to obtain the desired conductivities. The present data are also compared with those obtained by other investigators.
Keywords :
Conductivity; Contamination; Flashover; Glass; Insulation; Insulator testing; Laboratories; Slurries; Voltage; Water pollution;