DocumentCode :
1039135
Title :
Three-Phase Measurements of Resistance
Author :
Matsch, L.W. ; Basu, N.C. ; Horcher, G.R.
Author_Institution :
Illinois Instittste of Technology, Chicago, Ill.
Volume :
70
Issue :
1
fYear :
1951
fDate :
7/1/1951 12:00:00 AM
Firstpage :
350
Lastpage :
354
Abstract :
Unsymmetrical spacing of conductors produces errors in the values of a-c resistance measured on the individual conductors, of a 3-conductor system, with 3-phase current. The average of two sets of 3-phase measurements, one with positive sequence current and the other with negative sequence current gives the true value of conductor resistance. An analysis given in the Appendix evaluates the effect of unbalanced inductive reactance upon the measured resistance. Experimental data are shown which support the analysis.
Keywords :
Battery charge measurement; Circuits; Conductors; Current measurement; Current transformers; Electrical resistance measurement; Fluid flow; Fluid flow measurement; Phase measurement; Vibration measurement;
fLanguage :
English
Journal_Title :
American Institute of Electrical Engineers, Transactions of the
Publisher :
ieee
ISSN :
0096-3860
Type :
jour
DOI :
10.1109/T-AIEE.1951.5060414