• DocumentCode
    1039135
  • Title

    Three-Phase Measurements of Resistance

  • Author

    Matsch, L.W. ; Basu, N.C. ; Horcher, G.R.

  • Author_Institution
    Illinois Instittste of Technology, Chicago, Ill.
  • Volume
    70
  • Issue
    1
  • fYear
    1951
  • fDate
    7/1/1951 12:00:00 AM
  • Firstpage
    350
  • Lastpage
    354
  • Abstract
    Unsymmetrical spacing of conductors produces errors in the values of a-c resistance measured on the individual conductors, of a 3-conductor system, with 3-phase current. The average of two sets of 3-phase measurements, one with positive sequence current and the other with negative sequence current gives the true value of conductor resistance. An analysis given in the Appendix evaluates the effect of unbalanced inductive reactance upon the measured resistance. Experimental data are shown which support the analysis.
  • Keywords
    Battery charge measurement; Circuits; Conductors; Current measurement; Current transformers; Electrical resistance measurement; Fluid flow; Fluid flow measurement; Phase measurement; Vibration measurement;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1951.5060414
  • Filename
    5060414