Transient Overvoltages Caused by Monopolar Ground Fault on Bipolar DC Line: Theory and Simulation
Author :
Kimbark, Edward W.
Author_Institution :
Bonneville Power Administration
Issue :
4
fYear :
1970
fDate :
4/1/1970 12:00:00 AM
Firstpage :
584
Lastpage :
592
Abstract :
A short circuit from one pole to ground on a bipolar overhead dc line can produce an overvoltage factor as high as 2.2 per unit on the unfaulted pole, which may cause flashover of line insulation, thus converting a monopolar fault into a bipolar one. This is undesirable because a bipolar fault causes a greater disturbance to the power system than does a monopolar fault.
Keywords :
Adders; Circuit faults; Circuit simulation; Flashover; Insulation; Power system faults; Power system transients; Surges; Valves; Voltage control;