• DocumentCode
    1040611
  • Title

    Corona Location in Transformers by Radio Frequency Spectrum Analysis II. Application of Technique and Results of Measurements

  • Author

    Harrold, R.T.

  • Author_Institution
    Westinghouse Research Laboratories
  • Issue
    7
  • fYear
    1970
  • Firstpage
    1591
  • Lastpage
    1602
  • Abstract
    This paper gives a detailed account of the practical application of the technique of corona location in transformers by radio frequency spectrum analysis. The measurements are similar to the usual NEMA corona measurements taken at the bushing tap with a radio noise meter, except an X-Y recorder is used to plot the corona frequency spectrum and a current probe used at the neutral. The theory outlined in Part I is verified by extensive measurements taken from a model transformer using a pulse generator to represent a corona source, and by computer analysis of simulated transformer networks and by practical results.
  • Keywords
    Corona; Current measurement; Frequency measurement; Insulators; Noise measurement; Probes; Pulse generation; Pulse measurements; Radio frequency; Transformers;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1970.292806
  • Filename
    4074236