DocumentCode :
1040670
Title :
Eddy-Current Losses in Rectifier Transformers
Author :
Crepaz, Sergio
Author_Institution :
Department of Electrical Engineering, Polytechnic Institute of Milan
Issue :
7
fYear :
1970
Firstpage :
1651
Lastpage :
1656
Abstract :
Two methods are developed for evaluating the eddy- current losses occurring in a rectifier transformer during operation, i.e., when carrying pulsating currents. The first is based on the analysis of the whole waveshape; the second starts from the harmonic composition of current curves. Each system is useful from a different point of view, and both achieve the same results. Experimental measurements confirm the theoretical assumption, i.e., that eddy-current losses with pulsating currents can be some multiples higher than those evaluated by the tests prescribed by standards. Eddy-current loss evaluation is made for two-, six-, and twelve-pulse systems.
Keywords :
Circuits; Conducting materials; Frequency; Hydrogen; Loss measurement; Rectifiers; Shape; Testing; Transformers; Windings;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1970.292813
Filename :
4074243
Link To Document :
بازگشت