DocumentCode :
1040785
Title :
Transient Overvoltages Caused by the Initiation and Clearance of Faults on a 1100-kV System
Author :
Colclaser, R. Gerald, Jr. ; Wagner, Charles L. ; Buettner, Donald E.
Author_Institution :
Westinghouse Electric Corporation
Issue :
8
fYear :
1970
Firstpage :
1744
Lastpage :
1751
Abstract :
Overvoltages on UHV systems may be controlled to a level of 1.5 pu or less. Historically, lightning, line energizing, and line reenergizing overvoltages have been the primary factors in establishing power system design levels. At the new reduced levels, other transients must be considered. Fault initiation and fault clearing transients are investigated using different system configurations. Minimum levels are established by fault initiation transients. Fault clearing overvoltages can be controlled to corresponding levels by the insertion of opening resistors.
Keywords :
Circuit breakers; Circuit faults; Costs; Insulation; Lightning; Power system transients; Resistors; Surges; Switching circuits; Voltage control;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1970.292758
Filename :
4074258