DocumentCode
1040841
Title
Flashover Tests at Project UHV on Salt-Contaminated Insulators, Part II
Author
Kawai, Mikio
Author_Institution
Project UHV, General Electric Company
Issue
8
fYear
1970
Firstpage
1791
Lastpage
1799
Abstract
Results of experimental studies on the contamination flashover strength of EHV insulator strings are presented. The results compare favorably with a theoretical analysis by Boehne and Weiner in 1966-1967. Nonlinearity of insulation strength with insulator length has been investigated, employing a steam fog method to simulate natural humidity and fog. The nonlinearity is caused by nonuniform voltage distribution along contaminated insulator strings. Such nonuniform distribution is created by the capacitance of insulator units to ground. This relationship was clearly demonstrated by several indirect methods. The results should be very important in future contamination studies.
Keywords
Capacitance; Contamination; Flashover; Frequency; Humidity; Insulation; Insulator testing; Power transmission lines; System testing; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1970.292763
Filename
4074263
Link To Document