DocumentCode
1041639
Title
Detection of Slot Discharges in High-Voltage Stator Windings During Operation
Author
Johnson, John S. ; Warre, Mead
Author_Institution
Westinghouse Electric Corporation, East Pittsburgh, Pa.
Volume
70
Issue
2
fYear
1951
fDate
7/1/1951 12:00:00 AM
Firstpage
1998
Lastpage
2000
Abstract
A modified slot discharge detection method, which permits tests without Shutting down the machine or using auxilliary high-voltage test equipment, was investigated. The method involves connection of frequency sensitive equipment across all or part of the ntral impedance. Tests on eight vertical water wheel generators in the range of 20,000- to 40,000-kva capacity indicate that the method is generally applicable when there is a current transformer or some other impedance in the generator neutral.
Keywords
Bars; Coils; Current transformers; Frequency; Insulation; Power harmonic filters; Stator windings; Surface discharges; Surface impedance; Testing;
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Transactions of the
Publisher
ieee
ISSN
0096-3860
Type
jour
DOI
10.1109/T-AIEE.1951.5060664
Filename
5060664
Link To Document