DocumentCode :
1042132
Title :
Electrostatically Induced Voltages and Currents on Conducting Objects under EHV Transmission Lines
Author :
Tranen, J.D. ; Wilson, G.L.
Author_Institution :
Massachusetts Institute of Technology Department of Electrical Engineering
Issue :
2
fYear :
1971
fDate :
3/1/1971 12:00:00 AM
Firstpage :
768
Lastpage :
776
Abstract :
A study is made of the steady-state short circuit current Is.c., and open circuit voltage, Vo.c., to ground for conducting objects under E.H.V. transmission lines. This is carried out in a computer program and on a scaled down laboratory model of a transmission line. In addition, tests are conducted at the American Electric Power Service Corporation and Westinghouse Electric Corporation E.H.V. test site at Apple Grove, West Virginia[1]. The Apple Grove results are used for comparison with the other two approaches. Values of Is.c. within a few percent of the field data and of Vo.c. within about 30 percent are predicted by the computer program. For the transmission line model, the measured values of Is.c. are within a few percent of the Apple Grove measurements and the values of Vo.c. are within approximately 15 percent.
Keywords :
Capacitance; Distributed parameter circuits; Humans; Impedance; Power transmission lines; Steady-state; Transmission line measurements; Transmission line theory; Transmission lines; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1971.293104
Filename :
4074395
Link To Document :