    Conemaugh Project New Concepts for 500-kV System Protection

  • Author

    Holland, D.R. ; Paradis, G.D. ; Mcnair, G.E. ; Senuta, J. ; Van Zee, W.H.

  • Author_Institution
    Baltimore Gas & Electric Co.
  • Issue
    2
  • fYear
    1971
  • fDate
    3/1/1971 12:00:00 AM
  • Firstpage
    852
  • Lastpage
    858
  • Abstract
    The Conemaugh 500-kV system stability studies indicated that stability was achieved for all faults that were cleared in 4.5 cycles. If a breaker fails to clear a 3-phase fault, it is necessary to resort to a breaker failure timing scheme of 7.5 cycles and to down grade the fault to a single phase-to-ground fault by independent pole operation of the circuit breaker in order to maintain stability. To cover abnormal conditions when instability may still occur, out-of-step relays on generators are being applied to trip the unit when the first unstable swing appears in the unit transformer.
  • Keywords
    Circuit breakers; Circuit faults; Circuit stability; Flashover; Power system protection; Power system relaying; Protective relaying; Relays; Substations; Wind;