• DocumentCode
    1042496
  • Title

    Effect of approximate impedance formulae on the accuracy of transmission line modelling

  • Author

    Martins, T.F.R.D. ; Lima, A.C.S. ; Carneiro, Sandoval

  • Author_Institution
    Fed. Univ. of Rio de Janeiro, Rio de Janeiro
  • Volume
    1
  • Issue
    4
  • fYear
    2007
  • fDate
    7/1/2007 12:00:00 AM
  • Firstpage
    534
  • Lastpage
    539
  • Abstract
    It is well known that the accuracy of frequency-dependent line models in time-domain calculations relies on the equations that define the line propagation matrix H and characteristic admittance Yc. Therefore both modal-domain and phase-domain transmission line models are affected by the assumptions in the evaluation of the series impedance Z, namely, the formulation of the internal conductor and the ground return impedance. The complexities of the exact representation of these parameters have led investigators to propose approximate formulae, and several of these are available in the technical literature. This work examines the effects of these formulae on the calculation of matrices H and Yc on the time-domain responses of the line. Several possibilities have been tested. The results show that although the approximate methods can be used for overhead lines, caution is needed for underground cable systems.
  • Keywords
    electric impedance; time-domain analysis; transmission line matrix methods; approximate impedance formulae; frequency-dependent line models; ground return impedance; internal conductor; line propagation matrix; modal-domain transmission line models; overhead lines; phase-domain transmission line models; series impedance; underground cable systems;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission & Distribution, IET
  • Publisher
    iet
  • ISSN
    1751-8687
  • Type

    jour

  • DOI
    10.1049/iet-gtd:20060289
  • Filename
    4264407