• DocumentCode
    1042878
  • Title

    The Effect of High Currents on Disconnecting Switches With Special Reference to the Mechanical Stresses Resulting

  • Author

    Louis, H.C. ; Sinclair, C.T.

  • Author_Institution
    Consolidated Gas, Electric Light & Power Co., Baltimore, Md.
  • fYear
    1922
  • Firstpage
    271
  • Lastpage
    287
  • Abstract
    In the early days of the electrical industry, disconnecting switches adequately performed their functions without the use of locking devices, except perhaps in a few isolated cases, where the blades opened downward, and some mechanism was provided to hold the blade in against the action of gravity (when subjected to jars, vibration, etc.). The generating capacity of central stations at this time was relatively small. Hence, the short-circuit currents obtaining were relatively low, and the forces resulting were insufficient to overcome the friction and other resistance offered by the blade and to cause opening. With the increase in generating capacity came a formidable increase in the short-circuit currents, to such an extent that it was no uncommon for a disconnecting switch to open, causing considerable damage, with consequent demoralization of operation. The result was that there were attempts made to attach locks to switches already installed, and to design new switches of which the lock was an integral part. Many of these locks were found to be inadequate, as opening occurred in many instances. In an attempt to prevent the possible recurrence of such unfortunate incidents the tests described in the following paper were planned; it was hoped thereby to improve the class of service rendered the public and safe-guard the lives of our employees.
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1922.5060782
  • Filename
    5060782