DocumentCode
1043037
Title
Study of Corona Discharge Pattern on High Voltage Transmission Lines for Inspecting Faulty Porcelain Insulators
Author
Cheng, Yangchun ; Li, Chengrong ; Huang, Xingquan
Author_Institution
North China Electr. Power Univ., Beijing
Volume
23
Issue
2
fYear
2008
fDate
4/1/2008 12:00:00 AM
Firstpage
945
Lastpage
952
Abstract
The corona pattern from porcelain insulator strings on high voltage (HV) transmission lines has been investigated for inspecting faulty insulators on-line. Corona patterns from HV conductive line, metal accessory, and discharge patterns from bad connection, power stations, have also been studied for background pulse noise elimination. A pattern recognition method for inspecting faulty porcelain insulators is proposed, which consists of several criteria. It is found that the harmonics and carriers from the transmission lines influence the recognition seriously, which can be eliminated by choosing a high frequency band of sensors (2 MHz-20 MHz). Based on the above investigations, an instrument was developed and used on the field measurements in Lanzhou and Zhengzhou power utilities in China. The field results show a strong support for this method. On the measurement of 76 towers, the measuring accuracy of inspecting faulty insulators was about 87.5%.
Keywords
corona; discharges (electric); inspection; porcelain insulators; power transmission lines; background pulse noise elimination; corona discharge pattern; faulty porcelain insulators inspection; high voltage transmission lines; pattern recognition method; Corona; detection; faulty insulators; high-voltage techniques; inspection; insulators; noise; partial discharges; pattern recognition; porcelain insulators; pulse measurements; transmission lines;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on