• DocumentCode
    1043480
  • Title

    Overload Classification of Secondary Network Cables Modified Test Procedure

  • Author

    Hunter, C.H. ; Lamberton, S.P. ; McKean, A.L. ; Zazutak, T.J.

  • Author_Institution
    Cincinnati Gas & Electric Co.
  • Issue
    4
  • fYear
    1971
  • fDate
    7/1/1971 12:00:00 AM
  • Firstpage
    1873
  • Lastpage
    1883
  • Abstract
    This paper describes a new test procedure for determining the damage threshold temperature for secondary network cables. Present network cables generally have a maximum damage threshold temperature of 260°C and are protected by class L260 network limiters. The new procedure is considered suitable for evaluating cable designs for damage threshold temperatures up to 340°C, and adaptable for higher temperatures by increasing the rate of cooling of the conduit.
  • Keywords
    Cable insulation; Conductors; Insulation testing; Manufacturing; Polyethylene; Power industry; Round robin; Rubber; Temperature; Wire;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1971.293182
  • Filename
    4074537