DocumentCode :
1045151
Title :
Investigation of Corona Effects from Wet Bundle Conductions for Application to UHV Configurations
Author :
Pokorny, W.C. ; Schlomann, Robert H. ; Miller, Charles J., Jr. ; Barnes, Howard C.
Author_Institution :
American Electric Power Service Corp.
Issue :
1
fYear :
1972
Firstpage :
211
Lastpage :
222
Abstract :
An investigation into the corona effects of wet bundled conductors as determined by applied voltage, subconductor diameter and number of subconductors has been presented in Part I. Configurations tested include a range of subconductor diameters from 0.6" to 2.4", number of subconductors from 4 to 12, and applied phase-to- ground voltages to 550 kV. Part II is an analysis of the test data leading to general design considerations, including proposal of a universal curve of sound pressure level vs voltage.
Keywords :
Acoustic noise; Acoustic testing; Conductors; Corona; Laboratories; Microphones; Proposals; Rain; Spraying; Voltage;