• DocumentCode
    1045162
  • Title

    Project UHV Test Line Research on the Corona Performance of a Bundle Conductor at 1000 kV

  • Author

    Anderson, John G. ; Zaffanella, Luciano E.

  • Author_Institution
    General Electric Company
  • Issue
    1
  • fYear
    1972
  • Firstpage
    223
  • Lastpage
    232
  • Abstract
    A bundle of 4 subconductors 2-in (5.08 cm) in diameter was tested on the Project UHV single-phase test line. Radio noise, corona loss, audible noise, electrostatic field effects were continuously measured in order to investigate the effects of weather variables. Translation of the results to a 1000-kV, 3-phase line shows that audible noise will be the main obstacle to the use of this bundle.
  • Keywords
    Acoustic noise; Antenna measurements; Capacitors; Conductors; Corona; Instruments; Loss measurement; Noise measurement; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1972.293334
  • Filename
    4074703