DocumentCode :
1045674
Title :
Analysis of Power System Faults by Phase Impedance matrix Method: II-Simultaneous Unbalances and Transient Analysis
Author :
Dash, Pradipta K.
Author_Institution :
Regional Engineering College
Issue :
2
fYear :
1972
fDate :
3/1/1972 12:00:00 AM
Firstpage :
601
Lastpage :
610
Abstract :
Analysis of simultaneous unbalances and transient recovery voltages of power system has been undertaken in this paper. The approach is similar to the one developed in Part I of this paper. The method requires only the assembly of the nodal admittance or impedance matrices of various elements of a power system and subsequent solution of sets of linear algebraic equations subjected to constraints. The transient analysis of a power system having untransposed transmission lines can be carried out by the application of modified Foruier transform and the steady state theory of natural modes. Finally a digital computer can be programmed to calculate the magnitudes of the fault currents and active recovery voltages.
Keywords :
Admittance; Assembly systems; Equations; Impedance; Power system analysis computing; Power system faults; Power system transients; Transient analysis; Transmission line matrix methods; Voltage;