A Half Cycle Air Blast Generator Breaker for High Power Testing Fields
Author
Kriechbaum, Karl
Author_Institution
Allgemeine Elektricitÿts-Gesellschaft, AEG-TELEFUNKEN Hochspannungsschaltgerÿtefabrik
Issue
3
fYear
1972
fDate
5/1/1972 12:00:00 AM
Firstpage
747
Lastpage
753
Abstract
Generator breakers in high-power testing fields, the back-up breakers, have the function of safety breakers: they have to protect both the generator and the test breaker from being overstressed by a short-circuit current of undesired duration. The heavy short-circuit currents of modern generators enforce the development of generator circuit-breakers of high breaking capacities. In this paper a generator c. b. is described having a rated breaking capacity of 160 kA at a service voltage of 15.4 kV. This circuit-breaker is a half-cycle breaker capable of interrupting a symmetrical current at the first current zero passage. Due to its short minimum arcing time this breaker is suitable for syn- chronized breaking operations and so permits an economical testing of circuit-breakers. This testing method is also described.
Keywords
Air safety; Circuit testing; Explosion protection; Fluid flow; Frequency synchronization; Power generation; Power generation economics; Switches; Switchgear; Voltage;