• DocumentCode
    1045924
  • Title

    Validity of Unit Testing on Circuit-Breakers Exhibiting Statistically Varying Breaking Capacity

  • Author

    Braun, A.

  • Author_Institution
    Brown, Boveri & Co. , Ltd.
  • Issue
    3
  • fYear
    1972
  • fDate
    5/1/1972 12:00:00 AM
  • Firstpage
    791
  • Lastpage
    797
  • Abstract
    This paper gives some information about the problem of unit testing on high-voltage circuit-breakers. A theoretical investigation of the problem shows that statistical treatment is necessary and that the kind of the breaking process (dielectric or thermal reignition) is also very important. A large number of power tests with one and two units of an airblast breaker are presented. The experimental results agree well with the theoretical investigations. Therefore, direct or synthetic unit testing is not only an economical, but also a valid method for short circuit testing high-voltage circuit-breakers.
  • Keywords
    Breakdown voltage; Capacitors; Circuit breakers; Circuit testing; Dielectrics; IEC standards; Power generation economics; Resistors; Thermal conductivity; Thermal stresses;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1972.293408
  • Filename
    4074783