• DocumentCode
    1045975
  • Title

    Behavior of PWM Active Front Ends in the Presence of Parallel Thyristor Converters

  • Author

    Jalili, Kamran ; Weitendorf, Niels ; Bernet, Steffen

  • Author_Institution
    Berlin Univ. of Technol., Berlin
  • Volume
    55
  • Issue
    3
  • fYear
    2008
  • fDate
    3/1/2008 12:00:00 AM
  • Firstpage
    1035
  • Lastpage
    1046
  • Abstract
    This paper investigates the effects of grid voltage distortions caused by thyristor converters on the steady-state performance of a pulsewidth modulation (PWM) rectifier with dc voltage link for low-voltage applications. The disturbance transfer function of the current control loop is used to analyze the effects of grid distortions. Influences of the current controller, the phase-locked loop parameters, and the filter inductance on the generated current harmonics are presented. For existing grid voltage harmonics, the amplitude of the corresponding current harmonics are determined and compared to measured current harmonics using a 400-V 40-kW test bench consisting of a PWM rectifier with voltage dc link parallel to a 40-kW thyristor converter.
  • Keywords
    PWM rectifiers; distortion; phase locked loops; power grids; power system harmonics; thyristor convertors; PWM active front ends; current control loop; current harmonics; dc voltage link; filter inductance; grid voltage distortions; low-voltage applications; parallel thyristor converters; phase-locked loop parameters; power 40 kW; three-phase pulsewidth modulation rectifier; voltage 400 V; Harmonic distortion; PWM Active front ends; Thyristor converters; pulsewidth modulation (PWM) active front ends; thyristor converters;
  • fLanguage
    English
  • Journal_Title
    Industrial Electronics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0278-0046
  • Type

    jour

  • DOI
    10.1109/TIE.2008.917079
  • Filename
    4437767