DocumentCode :
1046232
Title :
Impedance and circulating Current Calculations for UD Multi-Wire Concentric Neutral Circuits
Author :
Smith, D.R. ; Barger, J.V.
Author_Institution :
Westinghouse Electric Corporation
Issue :
3
fYear :
1972
fDate :
5/1/1972 12:00:00 AM
Firstpage :
992
Lastpage :
1006
Abstract :
Two different methods are presented for calculating the impedances of UD multi-wire concentric neutral circuits. In the simplified method, the concentric neutral is represented as a uniform sheath and in the detailed method each wire of the neutral maintains its identity. It is shown that both methods essentially give the same results for both single-phase and three-phase circuits. The parameters affecting the division of current between the earth return path and the concentric neutral in single-phase circuits are defined. The effects of conductor spacing, concentric neutral radius, and concentric neutral resistance on earth-neutral circulating currents in three-phase circuits are presented. For single-phase circuits, it is shown that reducing concentric neutral size reduces neutral current but may cause an increase in neutral watts-loss.
Keywords :
Circuits; Conductivity; Conductors; Earth; Equations; Impedance; Power cables; Solids; Voltage control; Wire;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1972.293451
Filename :
4074812