• DocumentCode
    1046537
  • Title

    Current Interruption Ability of Vaccum Switches

  • Author

    Voshall, Roy E.

  • Author_Institution
    Westinghouse Research Laboratories
  • Issue
    3
  • fYear
    1972
  • fDate
    5/1/1972 12:00:00 AM
  • Firstpage
    1219
  • Lastpage
    1224
  • Abstract
    The ac current interruption ability of a vacuum switch has been examined and found to be a function of parameters which pertain to the electrodes contained in the switch and to the circuit to which the switch is connected. The dielectric recovery data for switched-off vacuum arcs are converted into a form that is applicable for determining the theoretical current interruption limit. Generalized plots of theoretical al current interruption limit versus the reciprocal of the RRRV of the circuit are given for switches having butt-type Cu or Ag electrodes. The current interruption limit of two different sizes of vacuum switches is calculated and checked against experimental test results.
  • Keywords
    Circuit testing; Dielectrics; Electrodes; Equations; Switches; Switching circuits; Temperature; Thermal conductivity; Vacuum arcs; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1972.293480
  • Filename
    4074841