DocumentCode
1046537
Title
Current Interruption Ability of Vaccum Switches
Author
Voshall, Roy E.
Author_Institution
Westinghouse Research Laboratories
Issue
3
fYear
1972
fDate
5/1/1972 12:00:00 AM
Firstpage
1219
Lastpage
1224
Abstract
The ac current interruption ability of a vacuum switch has been examined and found to be a function of parameters which pertain to the electrodes contained in the switch and to the circuit to which the switch is connected. The dielectric recovery data for switched-off vacuum arcs are converted into a form that is applicable for determining the theoretical current interruption limit. Generalized plots of theoretical al current interruption limit versus the reciprocal of the RRRV of the circuit are given for switches having butt-type Cu or Ag electrodes. The current interruption limit of two different sizes of vacuum switches is calculated and checked against experimental test results.
Keywords
Circuit testing; Dielectrics; Electrodes; Equations; Switches; Switching circuits; Temperature; Thermal conductivity; Vacuum arcs; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1972.293480
Filename
4074841
Link To Document