DocumentCode :
1046537
Title :
Current Interruption Ability of Vaccum Switches
Author :
Voshall, Roy E.
Author_Institution :
Westinghouse Research Laboratories
Issue :
3
fYear :
1972
fDate :
5/1/1972 12:00:00 AM
Firstpage :
1219
Lastpage :
1224
Abstract :
The ac current interruption ability of a vacuum switch has been examined and found to be a function of parameters which pertain to the electrodes contained in the switch and to the circuit to which the switch is connected. The dielectric recovery data for switched-off vacuum arcs are converted into a form that is applicable for determining the theoretical current interruption limit. Generalized plots of theoretical al current interruption limit versus the reciprocal of the RRRV of the circuit are given for switches having butt-type Cu or Ag electrodes. The current interruption limit of two different sizes of vacuum switches is calculated and checked against experimental test results.
Keywords :
Circuit testing; Dielectrics; Electrodes; Equations; Switches; Switching circuits; Temperature; Thermal conductivity; Vacuum arcs; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1972.293480
Filename :
4074841
Link To Document :
بازگشت