• DocumentCode
    1047042
  • Title

    60 HZ Behaviour of Vaccum Insulation in High Voltage Switchgear

  • Author

    Erven, Clifford C. ; van Heeswijk, R.G. ; Srivastava, K.D.

  • Author_Institution
    The Hydro-Electric Power Commission of Ontario
  • Issue
    4
  • fYear
    1972
  • fDate
    7/1/1972 12:00:00 AM
  • Firstpage
    1589
  • Lastpage
    1596
  • Abstract
    Vacuum has special properties which make it a potentially good insulating medium for the power industry but high voltage 60 Hz performance data is lacking. Experimental data is presented on the 60-Hz behaviour of vacuum insulation for gap lengths 0.5 to 2.0 cm between metal electrodes in a dynamically pumped system operating at 10-6 torr. The results are compared with the dc characteristics of vacuum insulation for similar test conditions. Prebreakdown phenomena and protrusion formations under 60 Hz voltage stress appear to be distinctly different. Specific recommendations are set out to guide further research effort, and to meet the particular requirements of vacuum insulation for high voltage power apparatus.
  • Keywords
    Breakdown voltage; Circuits; Electrodes; Gas insulation; Insulation testing; Power industry; Stress; Switchgear; Vacuum breakdown; Vacuum systems;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1972.293312
  • Filename
    4074892