DocumentCode
1047196
Title
Auxiliary Supply-Assisted 12-Pulse Phase-Controlled Rectifiers With Reduced Input Current Harmonics
Author
Fukuda, Shoji ; Hiei, Issei
Author_Institution
Grad. Sch. of Inf. Sci. & Technol., Hokkaido Univ., Sapporo
Volume
44
Issue
1
fYear
2008
Firstpage
205
Lastpage
212
Abstract
Three-phase thyristor rectifiers have been used in industries for obtaining a variable dc voltage, but they have a problem of including large lower-order harmonics in the input currents. For high-power applications, a 12-pulse configuration is useful for reducing the harmonics, but it still includes the (12 m plusmn1)th (m: integer) harmonics. In order to further reduce the harmonics, this paper proposes to insert an auxiliary supply producing a square wave voltage to the dc bus of a 12-pulse phase-controlled rectifier. Theoretical investigation to reduce harmonics is presented, and a strategy to control the auxiliary supply voltage based on pulse-width-modulation is proposed. Reduction in the current harmonics is verified by simulation and experimental results. The volt-ampere (VA) rating of the auxiliary supply is about 5% of the rectifier output.
Keywords
AC-DC power convertors; harmonics suppression; rectifying circuits; thyristor applications; auxiliary supply-assisted 12-pulse phase-controlled rectifiers; reduced input current harmonics; three-phase thyristor rectifiers; variable dc voltage; Active filters; Circuits; Diodes; Inductors; Power conversion harmonics; Power harmonic filters; Power system harmonics; Rectifiers; Thyristors; Voltage control; AC–DC power conversion; power conversion harmonics; power electronics; thyristor applications; thyristor converters;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.2007.912805
Filename
4439770
Link To Document