• DocumentCode
    1047458
  • Title

    Electrical Features of Raccoon Mountain Pumped-Storage Plant

  • Author

    Mock, Clarence H.

  • Author_Institution
    Tennessee Valley Authority
  • Issue
    5
  • fYear
    1972
  • Firstpage
    1875
  • Lastpage
    1880
  • Abstract
    This paper describes unique features of the electrical equipment and some of the considerations involved in its selection for a 1,700-MVA underground pumped-storage project with four reversible pump/turbines. Considerations of cost and maintenance of the machines, transmission system, and powerhouse construction led to selection of generator/motors with direct water-cooled stator and rotor windings, static-converter synchronous starting of pumps with synchronous dynamic braking, use of generator circuit breakers, and underground main transformers with self-contained 161-kV single-section cables having 1,100-ft change in elevation.
  • Keywords
    Circuit breakers; Costs; Machine windings; Power generation; Pumps; Rotors; Stator windings; Synchronous generators; Synchronous motors; Turbines;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1972.293513
  • Filename
    4074936