DocumentCode
1047485
Title
Voltage Escalation in the Switching of the Motor Control Circuit by the Vacuum Contactor
Author
Itoh, Toshio ; Murai, Yutaka ; Ohkura, Toshimoto ; Takami, Toshiji
Author_Institution
Mitsubishi Electric Corporation
Issue
5
fYear
1972
Firstpage
1897
Lastpage
1903
Abstract
A turn-to-turn fault of a high-voltage motor which was controlled by a vacuum contactor prompted this study. The study revealed that a voltage escalation can certainly occur by the repetition of re-ignitions as indicated by recent several papers,1,2, but the cause of the escalation is different from that reported. This paper presents a new theory for the voltage escalation, makes clear the conditions for the occurrence of the escalation, and leads to the conclusion that protectors are indispensable in the application of the contactors to the motor control circuit.
Keywords
Cables; Capacitance; Circuit testing; Inductance; Induction motors; Motor drives; Surge protection; Switches; Switching circuits; Voltage control;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1972.293516
Filename
4074939
Link To Document