Title :
Seismic Testing of Metal Clad and Metal Enclosed Switchgear Using Sine Beat Vibrations
Author :
Colaiaco, A.P. ; Albert, W.S.
Author_Institution :
Westinghouse Electric Corp.
Abstract :
Switchgear in nuclear generating stations must continue to perform its essential functions during earthquakes. Sine beat vibration testing has been used to demonstrate such reliability. These tests have shown that switchgear of standard design will withstand the earthquake levels currently prevalent in nuclear generating station specifications without strength failure or the degradation of the safe performance of principal functions.
Keywords :
Assembly; Earthquakes; Floors; Frequency; Nuclear power generation; Performance evaluation; Protection; Protective relaying; Switchgear; Testing;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1972.293534